Vent header slope criteria

asked May 11, 2014 in Process by cobiesmith (3,310 points)
How much is the adequate slope for vent headers?

1 Answer

0 votes
answered May 12, 2014 by RichS29 (4,320 points)

Vent headers must be provided with adequate slope for proper drainage and to element low points or pockets. API 521 5.4.1.3.7 recommends 1/4″ per 10 feet.

In addition to above recommendation following also needs to be considered:

  • Flare system route
  • Total elevation change from 1st discharge location to flare drum
  • PSV located higher than the Flare header
  • Piping support interval
...